The short version
- Your local fire marshal (the authority having jurisdiction, or AHJ) sets the minimum radio signal strength for fire department communications in new and existing buildings. §633.202(18)(a)
- Buildings that don't meet it can be required to install a two-way radio communication enhancement system: a BDA and DAS. §633.202(18)(c)
- Some buildings are exempt, including one- and two-family homes and townhouses, and buildings under 12,000 square feet with no underground areas. §633.202(18)(h)
- The statute's dates for existing high-rise buildings, a permit application by January 1, 2024 and compliance by January 1, 2025, have passed. §633.202(18)(a)
- Any new system, or any change to an existing one, needs the express consent of the frequency license holder. §633.202(18)(d)
Who decides
Florida law puts the local authority having jurisdiction in charge: it “shall determine the minimum radio signal strength for fire department communications in all new and existing buildings.” Except where the statute says otherwise, all new and existing buildings must meet the minimum radio signal strength requirements in the Florida Fire Prevention Code. §633.202(18)(a)–(b)
The AHJ may require a system where a building's interior falls short, and may require an assessment of a building's interior radio coverage. For existing buildings, that assessment can't be required more often than once every 3 years for high-rises and buildings over 12,000 total gross square feet, or once every 5 years for other buildings, unless the building undergoes a Level III alteration or reconstruction, a public-safety agency reports that its radios failed inside, or the building is found to be an imminent life safety threat to first responders. §633.202(18)(c)
The same subsection limits local rules: the AHJ may not enforce requirements more stringent than the Florida Fire Prevention Code and the statute for the requirement for, design of, or installation of a system. Fire marshals do still publish their own procedures and checklists, so ask yours for theirs. §633.202(18)(i)
If the public-safety signal is already inadequate outside the building, as determined by the AHJ, neither a system nor a coverage assessment is required. §633.202(18)(e)
Which buildings
The statute lists buildings that don't have to meet the minimum signal strength or have an assessment:
- One- and two-family dwellings and townhouses.
- Buildings under 12,000 total gross square feet with no underground areas.
- Apartments and transient public lodging under three stories, with direct access from the unit to an exterior means of egress.
- Wood-frame apartment buildings 75 feet or less in height with fewer than 150 units, where every unit discharges to the exterior or to a corridor leading directly to an exit. The owner shows wood-frame construction with the building permit documents.
Existing buildings and the dates
The statute gave existing high-rise buildings, including existing high-rise apartment buildings, until January 1, 2024 to apply for a permit and until January 1, 2025 to comply. Both dates have passed. If an existing high-rise isn't compliant, talk to your fire marshal about where it stands. §633.202(18)(a)
Two protections for owners remain. If the AHJ changes its own radio system in a way that forces changes to existing building systems, it must give owners at least 180 days' notice. And an AHJ that requires an existing building to retrofit its system after the statutory dates must give the owner at least 1 year to finish, counted from the notice of code violation. §633.202(18)(f)–(g)
New construction
If the radio assessment of a new building shows a system is required, a licensed contractor submits a design to the AHJ. The AHJ may not withhold a temporary certificate of occupancy based solely on the need for the system. Once the design is approved, the system must be installed within 12 months after the temporary certificate of occupancy is issued. §553.79(22)
The code and the standard
The Florida Fire Prevention Code in effect today is the 8th edition, effective December 31, 2023. It is built on the Florida editions of NFPA 1 and NFPA 101 (2021). For in-building emergency responder radio, the publications it references include NFPA 1221 (2019 edition). State Fire Marshal; Rule 69A-60.005
NFPA has since folded NFPA 1221 into NFPA 1225, Standard for Emergency Services Communications, first published as the 2022 edition. The State Fire Marshal lists a 9th edition of the Florida Fire Prevention Code with an effective date of December 31, 2026, so the referenced editions may change. Ask your fire marshal which edition they will apply to your project. NFPA 1225; State Fire Marshal
What the standards ask for
Side by side, the core figures in the two editions. The NFPA 1221 (2019) column is as quoted in Orange County Fire Rescue's contractor checklist, one Florida AHJ's published document; the NFPA 1225 (2022) column is from the standard itself. Orange County Fire Rescue; NFPA 1225
| Requirement | NFPA 1221 (2019) | NFPA 1225 (2022) |
|---|---|---|
| Coverage in critical areas1221 §9.6.7.3; 1225 §18.8.3 | 99% of floor area | 99% of floor area |
| Coverage in general building areas1221 §9.6.7.4; 1225 §18.8.4 | 90% of floor area | 95% of floor area |
| Radio quality1221 §9.6.8; 1225 §18.9 | DAQ 3.0 | DAQ 3.0, downlink and uplink |
| Secondary (backup) power1221 (section not cited in the checklist); 1225 §18.13.2 | 12 hours at 100% capacity | 12 hours at 100% capacity |
Critical areas in NFPA 1225 include fire command centers, fire pump rooms, exit stairs, exit passageways, elevators, elevator lobbies, standpipe cabinets, sprinkler sectional valve locations, and other areas the AHJ deems critical. NFPA 1225 §18.8.3
NFPA 1225 (2022) also requires:
- Plans approved before installation, and written authorization from the frequency license holder before the system is activated. §18.7
- Supervisory signals to the fire alarm system for faults, low battery and loss of AC power, and a dedicated annunciator in the fire command center. §18.14
- Repeaters, signal boosters, power supplies and related components listed to UL 2524. §18.12.1.3
- A system test, documented and signed by a person approved by the AHJ, at acceptance and once every 12 months. §20.3.10
Its annex describes the usual test method: a grid of 20 cells laid over each floor, with readings at the center of each cell. Your AHJ sets the procedure. Annex A.20.3.10
FCC rules
Under federal rules, anyone other than the licensee who operates a signal booster must have the express consent of the licensee of the frequencies it amplifies, kept in a recordable format that can be shown to the FCC. Class B signal boosters, broadband units with a passband wider than 75 kHz, must be registered in the FCC's signal booster database. 47 CFR 90.219
Florida law separately requires the frequency license holder's express consent for any new system and any change to an existing one. §633.202(18)(d)
Sources
- Section 633.202(18), Florida Statutes (2026)The Florida Legislature
- Section 553.79(22), Florida Statutes (2026)The Florida Legislature
- Florida Fire Prevention Code: 8th edition (effective December 31, 2023) and 9th edition (effective December 31, 2026)Florida Division of State Fire Marshal
- Rule 69A-60.005, F.A.C.: publications referenced in NFPA 1 and NFPA 101, Florida 2021 editions (lists NFPA 1221, 2019 edition)Florida Administrative Code
- NFPA 1225, Standard for Emergency Services Communications, 2022 edition: chapter 18 and section 20.3.10National Fire Protection Association. Read from the 2022 free-access text. TIAs and errata may apply.
- DAS checklist for contractors (Florida Fire Prevention Code 8th edition, NFPA 1221 2019)Orange County Fire Rescue. An example of a Florida AHJ's own checklist. Other AHJs publish their own.
- 47 CFR 90.219, Use of signal boostersElectronic Code of Federal Regulations